RESOURCES / Ohr

Minimum dimensions for fire resistance of private residences constructed in reinforced concrete

Minimum periods of structural fire resistance and dimensional guidance for reinforced-concrete private residences, referencing the UBBL and structural design standards.

Ohr Notes

Ohr Notes 008 · Rev 00 February 2023

Note 8 - 1

Photograph: C2 Builder.

In Malaysia, like most countries, it is a statutory requirement that in the event of a fire, a building has to be able to maintain its structural integrityi for a given minimum period. This duration is termed the minimum period of fire resistanceii.

Minimum period of fire resistance

This has to be determined in accordance with the Ninth Schedule of the Uniform Building By-Laws (UBBL) and is dependent on the type of use and height of the building structure.

For private residences: the above-ground structure needs to have a minimum resistance period of 30 minutes for three storeys and below, and 60 minutes for above. Basements require 60 minutes for four storeys and below, and 90 minutes for above.

Purpose groupMaximum dimensionMinimum period of fire resistance (hours)
Height (m)Floor area (m²)Cubic capacity (m³)Ground or upper storeyBasement storey
Small residential — house of not more than 3 storeysNLNLNL½1(a) (x)
Small residential — house of 4 storeysNL250NL1(b)1 (x)
Small residential — house of any number of storeysNLNLNL11½
Institutional282,000NL11½
Institutional — over 28 mover 282,000NL1½2
Extract from the Ninth Schedule of the UBBL, as reproduced in the February 2023 publication. Original notation retained; refer to the full Schedule for qualifications and exceptions.

Minimum dimensions

As it is a statutory requirement for buildings in Malaysia to be designed in accordance with the UBBL, the minimum dimensions given in the Ninth Schedule of the UBBL must be met.

Although it is statutorily sufficient to meet the minimum dimensions given in the UBBL, where the code of practice adopted for the design of the structure gives a larger value, it may be best practice to adopt the larger value as codes of practice are reviewed and updated more frequently than the UBBL. This is something to be discussed and agreed with the client.

The minimum dimensions needed in accordance with the UBBL, British Standard and Eurocode are summarised below, as published in February 2023. The dimensions of a structural element will be the largest of what is needed for fire resistance and other design considerations (collapse under permanent loads, deflection, etc.).

Slab

Fire resistanceUBBLBritish StandardEurocode
30 minutes—¹75 mm60 mm
60 minutes—¹95 mm80 mm

¹ Not defined.

Beam — minimum width

Fire resistanceUBBLBritish StandardEurocode²
30 minutes—¹200 mm80–200 mm
60 minutes—¹200 mm120–300 mm

¹ Not defined. ² The exact value has to be calculated based on several factors.

Column

Fire resistanceUBBL: fully exposed¹UBBL: built into wall²BS: fully exposed³BS: 50% exposed³BS: one face exposed³Eurocode: exposed more than one side³Eurocode: exposed one side
30 minutes150 mm75 mm150 mm125 mm100 mm200–300 mm155 mm
60 minutes200 mm75 mm200 mm160 mm120 mm200–350 mm155 mm

¹ UBBL allows smaller dimensions if reinforced plaster, vermiculite or fire-rated plasterboard encasement is used. Refer to the Ninth Schedule for more details.

² Fully built into a full-height wall that extends 600 mm on either side of the column, has the same fire rating as the column, and with no part of the column projecting beyond the face of the wall. 63 mm if 12.5 mm thick vermiculite gypsum plaster is used.

³ Definition of exposure: when a face of a column is exposed to fire. Exact values are to be computed based on several factors.

Wall

Fire resistanceUBBL¹BS: p < 0.4%²BS: 0.4% < p < 1%BS: p > 1%Eurocode³
30 minutes75 mm150 mm100 mm75 mm100–120 mm
60 minutes75 mm100 mm120 mm75 mm110–140 mm

¹ 63 mm if 12.5 mm thick vermiculite gypsum plaster is used. ² p is the percentage of reinforcement provided. ³ The exact value has to be computed based on several factors.

References

  1. Uniform Building By-Laws 1984, Amendment 2021.
  2. Figure 3.2, BS 8110-1-1:1997.
  3. BS EN 1992-1-2:2004.

i The UBBL gives this technical definition for fire resistance period: the period for which an element will meet the requirements in respect of transmission of heat or resistance to collapse with passage of flame when tested in accordance with BS 476.

ii Structural integrity in terms of fire resistance is the ability of the structure or structural element to provide an appropriate degree of resistance to flame penetration, heat transmission and collapse.

iii The minimum dimensions detailed are from part one of the British Standard and Eurocode. However, part two of the respective codes can be used for more detailed assessments that may result in more economical solutions.

Revision 00: February 2023